Insulation Resistance Measurement

WHAT IS AN INSULATION TEST?


An insulation test (ISO test) is an electrical test that is carried out to check the insulation integrity of an electrical device or electrical system. During this test, the insulation resistance between the live parts and the non-current-carrying parts of the device is measured.

 

This is done by applying a high voltage to the parts to be tested and measuring the insulation resistance.A high insulation resistance measurement indicates that the insulation is intact and that there are no unwanted electrical leakage currents. An insulation test is important to ensure the safety of electrical devices and to minimise the risk of electric shocks or other electrical hazards.

 

HOW IS AN INSULATION TEST CARRIED OUT?

 

Here are the basic steps for carrying out an insulation test:

 

  1. Preparation: Make sure that the device is switched off and disconnected from the power supply. Also check that the tester is working properly and is calibrated.

  2. Connecting the test device: Connect the test device to the device connections to be tested. Ensure that the connection is firm and secure.

  3. Setting the test voltage: Set the desired test voltage on the test device. The test voltage depends on the specific requirements of the device or the standard to be tested.

  4. Performing the test: Switch on the tester and start the insulation test. The tester generates a high voltage which is applied to the device or component. The test duration may vary depending on the requirements.

  5. Evaluation of the result: The measurement results are given in ohms. There are various standards and regulations that specify the minimum values that must be observed for the insulation resistance.

 

The safety guidelines in accordance with EN 50191 must be observed throughout the entire procedure. It is important that the test is carried out by trained personnel, as high voltages are used and this can lead to dangerous situations. In addition, the cables or devices to be tested should be de-energised before the test in order to avoid accidents.

 

 

Items 1-10 of 57

Page
per page
Set Descending Direction
  1. ATS 400 Bild 1
    ATS400 UGIPe-30L30L32-1G-OCV1000
    Article number 212987
    • HV DC - High Voltage Testing
      50,0 - 3000 V DC, 0,01 - 2,00 mA, current limited, earthed on one side, active discharge, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 1000 MΩ (opt. 10 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • PE - Testing of Protective Earth
      2,0 - 32,0 A AC/DC (opt. up to 40 A), 1 - 500 mΩ, < 12 V, 4 - wire measurement
    • Contacting options
      CCCG
  2. ATS 400 Bild 1
    ATS400 UHGI-507030Le
    Article number 211988
    • HV AC - High Voltage Testing
      100,0 - 5000 V AC, 0,01 - 100,00 mA (opt. from 1 nA), potential free, ramp, discharge monitoring
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,01 - 100,00 mA (opt. from 1 nA), max. 500VA, potential free, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • Contacting options
      CC
  3. ATS 400 Bild 1
    ATS400 UGIPR-707032
    Article number 211718
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,10 - 100 mA, potential free, ramp, discharge monitoring
    • ISO - Insulation Testing
      150,0 - 7000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), potential free, ramp, discharge monitoring
    • PE - Testing of Protective Earth
      2,0 - 32,0 A AC/DC (opt. up to 40 A), 1 - 500 mΩ, < 12 V
    • R - Resistance Measurement DC4
      1 µA - 2 A, 0,01 µΩ - 2,2000 MΩ, 4-wire measuring technique, contact monitoring, automatic measuring range selection, optional 11 fixed measuring ranges
    • Contacting options
      CCCG
  4. ATS 400 Bild 1
    ATS400 UHGIPRFA-507030L32
    Article number 212183
    • HV AC - High Voltage Testing
      100,0 - 5000 V AC, 0,01 - 100,00 mA (opt. from 1 nA), potential free, ramp, discharge monitoring
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,10 - 100 mA, potential free, active discharge, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • PE - Testing of Protective Earth
      2,0 - 32,0 A AC/DC (opt. up to 40 A), 1 - 500 mΩ, < 12 V
    • R - Resistance Measurement DC4
      1 µA - 2 A, 0,01 µΩ - 2,2000 MΩ, 4-wire measuring technique, contact monitoring, automatic measuring range selection, optional 11 fixed measuring ranges
    • FCT variable - Function Measurement
      1,0 - 270,0 V AC, 45- 65 Hz, 500 VA, electronic source
    • AI - Leakage Current Testing
      0,1 µA - 30,00 mA, 0 - 1 MHz, EN 60601-1 (medical), EN 60990-1 (industrial), opt. other standards
    • Contacting options
      CCCG
  5. ATS 400 Bild 1
    ATS400 UHGIPF-507030L32
    Article number 212495
    • HV AC - High Voltage Testing
      100,0 - 5000 V AC, 0,01 - 100,00 mA (opt. from 1 nA), potential free, ramp, discharge monitoring
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,10 - 100 mA, potential free, active discharge, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • PE - Testing of Protective Earth
      2,0 - 32,0 A AC/DC (opt. up to 40 A), 1 - 500 mΩ, < 12 V
    • FCT variable - Function Measurement
      1,0 - 270,0 V AC, 45- 65 Hz, 500 VA, electronic source
    • Contacting options
      CCCG
  6. ATS 400 Bild 1
    ATS400 UHGIPR-50707032
    Article number 211445
    • HV AC - High Voltage Testing
      100,0 - 5000 V AC, 0,01 - 100,00 mA (opt. from 1 nA), potential free
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,01 - 100,00 mA (opt. from 1 nA), max. 500VA, potential free
    • ISO - Insulation Testing
      150,0 - 7000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), potential free
    • PE - Testing of Protective Earth
      2,0 - 32,0 A AC/DC (opt. up to 40 A), 1 - 500 mΩ, < 12 V
    • R - Resistance Measurement DC4
      1 µA - 2 A, 0,01 µΩ - 2,2000 MΩ, 4-wire measuring technique, contact monitoring, automatic measuring range selection, optional 11 fixed measuring ranges
    • Contacting options
      CCCG
  7. ATS 400 Bild 1
    ATS400 UGI-50L30L
    Article number 209631
    • HV DC - High Voltage Testing
      150,0 - 5000 V DC, 0,01 - 5,00 mA, current limited, potential free, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • Contacting options
      CC
  8. ATS 400 Bild 1
    ATS400 UGIR-30L30L
    Article number 211382
    • HV DC - High Voltage Testing
      50,0 - 3000 V DC, 0,01 - 2,00 mA, current limited, earthed on one side, active discharge, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, earthed on one side, active discharge, ramp, discharge monitoring
    • R - Resistance Measurement DC4
      1 µA - 2 A, 0,01 µΩ - 2,2000 MΩ, 4-wire measuring technique, contact monitoring, automatic measuring range selection, optional 11 fixed measuring ranges
    • Contacting options
      CCC
  9. ATS 400 Bild 1
    ATS400 UGI-30L10L
    Article number 205553
    • HV DC - High Voltage Testing
      150,0 - 3000 V DC, 0,01 - 2,00 mA, active discharge, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 1000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), current limited accor. EN 50191, active discharge, ramp, discharge monitoring
    • Contacting options
      CC
  10. ATS 400 Bild 1
    ATS400 UGIR-7030L
    Article number 211647
    • HV DC - High Voltage Testing
      150,0 - 7000 V DC, 0,01 - 100,00 mA (opt. from 1 nA), max. 500VA, potential free, ramp, discharge monitoring
    • ISO - Insulation Testing
      50,0 - 3000 V DC, 500,0 kΩ - 400,0 MΩ (opt. 5 GΩ), earthed on one side, active discharge, ramp, discharge monitoring
    • R - Resistance Measurement DC4
      1 µA - 2 A, 0,01 µΩ - 2,2000 MΩ, 4-wire measuring technique, contact monitoring, automatic measuring range selection, optional 11 fixed measuring ranges
    • Contacting options